THE ROLE OF THE AUTOMATIC FIRE EXTINGUISHING INSTALLATION FOR WAREHOUSE SECURITY Cover Image

ROLUL INSTALAȚIEI DE STINGERE AUTOMATĂ A INCENDIILOR PENTRU SECURITATEA DEPOZITELOR
THE ROLE OF THE AUTOMATIC FIRE EXTINGUISHING INSTALLATION FOR WAREHOUSE SECURITY

Author(s): Emanuil-Petru Ovadiuc, Manuel Șerban
Subject(s): Politics / Political Sciences, Politics, Law, Constitution, Jurisprudence, Library and Information Science, Environmental Geography, Education and training, Security and defense, Military policy, Peace and Conflict Studies, Labour and Social Security Law
Published by: Editura Universitară
Keywords: pyrosim; temperature; firefighter; warehouse; sprinklers;
Summary/Abstract: The article describes a simulation of a fire in a plastic and polypropylene storage warehouse using Pyrosim software. The warehouse has a 40 cm thick concrete floor and is 34.02 m long, 23.73 m wide, and 8.38 m high. Temperature distribution during the fire was monitored using vertical and horizontal temperature plans. The highest temperature of 1020°C was recorded in the vertical plan passing through the fire, and at a height of 1.7 meters, the temperature reached 120°C, making it difficult for firefighters to enter the storage area. Finally, the article highlights the importance of an automatic sprinkler extinguishing system to prevent explosions and rapid fire spread throughout the warehouse.

  • Page Range: 233-241
  • Page Count: 10
  • Publication Year: 2023
  • Language: Romanian